Question 1. During a cooling-system inspection, a technician measures a refrigerant suction pressure corresponding to a saturation temperature of 42°F. The actual suction-line temperature is 58°F. What is the measured superheat?
A. 12°F
B. 16°F
C. 20°F
D. 100°F
Correct Answer: B. 16°F
Answer Explanation:
Option B is correct because superheat is calculated by subtracting the refrigerant saturation temperature from the actual suction-line temperature. The calculation is 58°F − 42°F = 16°F. Superheat indicates how much the refrigerant vapor temperature exceeds its saturation temperature at the measured pressure. This measurement helps a technician evaluate refrigerant feeding and evaporator operation. However, the acceptable superheat depends on the equipment design, metering device, operating load, and manufacturer’s specifications. A technician should not determine refrigerant charge from superheat alone without considering other operating measurements. Accurate diagnosis requires stable system conditions and the correct pressure-temperature relationship for the refrigerant being used.
Why the other options are incorrect:
Option A is incorrect because the difference between the two supplied temperatures is not 12°F.
Option C is incorrect because 20°F exceeds the calculated temperature difference.
Option D is incorrect because adding the temperatures does not calculate superheat.
Quick Study Guide:
Superheat = actual suction-line temperature − refrigerant saturation temperature.
Use the correct refrigerant pressure-temperature chart.
Compare readings with the manufacturer’s operating specifications.
Evaluate the full system before adjusting refrigerant charge.
Question 2. A commercial air-conditioning compressor repeatedly trips its overload protector. A technician confirms that the supply voltage is within the manufacturer’s specified range, the condenser coil is clean, and the condenser fan operates correctly. Compressor current remains above the rated operating current after the system stabilizes. What should the technician do next?
A. Increase the circuit-breaker rating to prevent nuisance trips.
B. Add refrigerant until the suction pressure increases.
C. Bypass the compressor overload protector and observe the system.
D. Measure operating pressures and electrical current against manufacturer specifications and investigate possible mechanical, electrical, or refrigerant-related causes.
Correct Answer: D. Measure operating pressures and electrical current against manufacturer specifications and investigate possible mechanical, electrical, or refrigerant-related causes.
Answer Explanation:
Option D is correct because excessive compressor current can result from several conditions, including abnormal operating pressures, incorrect refrigerant charge, electrical supply problems, winding faults, or internal mechanical damage. The clean condenser coil and functioning fan eliminate two possible causes but do not establish the underlying fault. The technician should collect relevant pressure, temperature, voltage, and current measurements and compare them with the equipment manufacturer’s specifications. The investigation should follow safe diagnostic procedures and account for the compressor’s operating conditions. Replacing components or adding refrigerant without supporting evidence can worsen the problem. The overload protector must remain functional because it protects the compressor against damaging operating conditions.
Why the other options are incorrect:
Option A is incorrect because increasing breaker capacity without verifying circuit requirements can create a serious electrical hazard.
Option B is incorrect because adding refrigerant without confirming an undercharge may cause additional operating problems.
Option C is incorrect because bypassing overload protection exposes the compressor to potential damage and unsafe operating conditions.
Quick Study Guide:
Compare compressor current with the rated operating specifications.
Check electrical conditions and refrigeration pressures before deciding on a repair.
Do not assume that one symptom identifies a single cause.
Never bypass compressor overload protection.
Question 3. A contractor is reviewing a duct system for a building where several rooms receive insufficient airflow. The supply blower operates at the specified speed, but measurements show excessive external static pressure. Inspection reveals that the main supply duct is undersized and several branch dampers are almost fully closed. Which corrective approach is most appropriate?
A. Evaluate and correct duct sizing and damper settings, then measure airflow and static pressure again.
B. Increase the refrigerant charge to compensate for the reduced airflow.
C. Replace the thermostat with a model that has a lower temperature setting.
D. Seal the return-air grille to increase the pressure available at the supply registers.
Correct Answer: A. Evaluate and correct duct sizing and damper settings, then measure airflow and static pressure again.
Answer Explanation:
Option A is correct because undersized ducts and excessively restricted dampers increase resistance to airflow. This resistance can raise external static pressure and reduce the volume of air delivered to occupied spaces. The contractor should evaluate the duct layout, calculate or verify appropriate duct dimensions, inspect restrictions, and adjust dampers according to the system design. After making corrections, airflow and static pressure should be measured again to confirm that the system operates within its specified range. Simply increasing blower speed may not solve an undersized duct problem and can increase noise or energy consumption. Proper air distribution supports comfort, heat transfer, and overall equipment performance.
Why the other options are incorrect:
Option B is incorrect because refrigerant charge does not correct a restriction in the air-distribution system.
Option C is incorrect because changing the thermostat setting does not resolve excessive duct resistance.
Option D is incorrect because restricting return airflow can further reduce system airflow and impair equipment performance.
Quick Study Guide:
Duct resistance affects airflow and external static pressure.
Check duct dimensions, obstructions, and damper positions.
Verify airflow after making adjustments.
Do not use refrigerant charge to compensate for duct-design problems.
Question 4. A technician replaces a damaged section of refrigerant piping in a split air-conditioning system. Before charging the system, the technician must verify that the repaired section is leak-free. Which procedure is most appropriate?
A. Charge the system immediately because brazed joints are automatically leakproof.
B. Pressurize the circuit with oxygen and inspect the joints.
C. Use an approved inert test gas, suitable pressure-regulating equipment, and a pressure within the manufacturer’s specified limits; check for leaks and evacuate the system before charging.
D. Use ordinary compressed air above the component pressure rating to reveal small leaks quickly.
Correct Answer: C. Use an approved inert test gas, suitable pressure-regulating equipment, and a pressure within the manufacturer’s specified limits; check for leaks and evacuate the system before charging.
Answer Explanation:
Option C is correct because repaired refrigeration piping must be checked for leaks before the system is returned to service. Dry nitrogen is commonly used for this purpose when allowed by the manufacturer’s procedures. A suitable regulator and pressure-rated testing equipment are essential, and the test pressure must remain within the specified limits of all connected components. Any leaks must be corrected and the circuit retested. Once the pressure test is successful, the system must be evacuated using the prescribed procedure to remove air and moisture before refrigerant charging. Pressure testing and evacuation have different purposes: one verifies circuit integrity, while the other removes unwanted gases and moisture that could affect system reliability.
Why the other options are incorrect:
Option A is incorrect because brazed joints can still leak and must be tested.
Option B is incorrect because oxygen can react dangerously with refrigeration oil under pressure.
Option D is incorrect because compressed air can introduce moisture and oxygen, while excessive pressure can damage equipment.
Quick Study Guide:
Use approved inert gas for pressure testing when specified.
Never use oxygen or ordinary compressed air to pressure-test refrigeration circuits.
Stay within the applicable pressure limits.
Complete evacuation before charging the system.
Question 5. A contractor is selecting a replacement air-conditioning unit for a commercial building. The existing equipment has a history of long operating cycles and uneven temperatures between rooms. Which approach is most appropriate before selecting the replacement unit?
A. Select a unit with substantially greater capacity than the existing system to eliminate long operating cycles.
B. Perform an appropriate heating and cooling load calculation, evaluate the building’s ductwork and airflow, and select equipment suited to the calculated load and installation conditions.
C. Choose the unit with the highest nominal capacity available within the project budget.
D. Match the replacement unit to the existing equipment capacity without checking the building’s current requirements.
Correct Answer: B. Perform an appropriate heating and cooling load calculation, evaluate the building’s ductwork and airflow, and select equipment suited to the calculated load and installation conditions.
Answer Explanation:
Option B is correct because equipment selection should be based on the building’s actual heating and cooling requirements rather than the capacity of the existing unit alone. An appropriate load calculation considers factors such as building size, insulation, window characteristics, orientation, occupancy, ventilation, and local design conditions. The contractor should also evaluate duct sizing, airflow, and distribution problems that may contribute to uneven temperatures. Oversized equipment can cycle frequently, provide inadequate humidity control, and operate less efficiently under some conditions. Undersized equipment may struggle to maintain the desired indoor temperature during peak conditions. Proper sizing and system evaluation help improve comfort, efficiency, and long-term reliability.
Why the other options are incorrect:
Option A is incorrect because excessive capacity can create short cycling and humidity-control problems.
Option C is incorrect because the highest-capacity unit is not necessarily suitable for the building’s load.
Option D is incorrect because the existing equipment may have been incorrectly sized or the building requirements may have changed.
Quick Study Guide:
Calculate the building’s heating and cooling loads before selecting equipment.
Consider insulation, windows, occupancy, ventilation, and local climate.
Evaluate ductwork and airflow when investigating uneven temperatures.
Avoid selecting equipment based solely on the old unit’s capacity.