Question 1. A technician is diagnosing a split air-conditioning system that uses a thermostatic expansion valve (TXV). The evaporator is operating with higher-than-normal superheat, while the measured subcooling is within the manufacturer’s specified range. The air filter is clean, and indoor airflow has been verified. Which condition should the technician investigate first?
A. Excessive refrigerant charge causing liquid to accumulate in the condenser
B. A reversing valve stuck in the heating position
C. A restriction at the metering device or an inadequate refrigerant feed through the TXV
D. Excessively low condenser airflow caused by a dirty outdoor coil
Correct Answer: C. A restriction at the metering device or an inadequate refrigerant feed through the TXV
Answer Explanation:
Option C is correct because high evaporator superheat indicates that the refrigerant leaving the evaporator is warmer than its saturation temperature by an unusually large amount. When subcooling remains within the manufacturer’s specified range and indoor airflow is adequate, an insufficient refrigerant feed through the TXV or a restriction near the metering device becomes an important possibility. The technician should verify pressure and temperature measurements, confirm the correct refrigerant saturation values, inspect the TXV sensing bulb and equalizer arrangement, and check for restrictions. These readings do not prove a single fault by themselves, so the diagnosis must be confirmed through systematic testing. Correct refrigerant feeding is essential for evaporator performance and compressor protection.
Why the other options are incorrect:
Option A is less consistent with the stated normal subcooling and high-superheat pattern, although charge must be evaluated using the manufacturer’s procedure.
Option B is not supported by the symptoms because no evidence indicates a reversing-valve malfunction.
Option D is less likely because restricted condenser airflow commonly affects condensing pressure and temperature, rather than directly establishing a metering-device fault.
Quick Study Guide:
Superheat indicates how much vapor temperature exceeds its saturation temperature.
High superheat can indicate insufficient refrigerant feed to the evaporator.
Normal subcooling does not independently prove that the refrigerant charge is correct.
Confirm TXV operation, restrictions, and measurements before replacing components.
Question 2. A gas-fired furnace repeatedly shuts down shortly after ignition. The burners light normally, but the flame disappears after several seconds. The control board indicates a flame-proving fault. What should the technician check first?
A. The flame sensor condition, electrical connection, grounding, and flame-signal measurement according to the manufacturer’s instructions
B. The evaporator coil’s refrigerant charge
C. The cooling system’s indoor blower speed
D. The thermostat’s cooling differential setting
Correct Answer: A. The flame sensor condition, electrical connection, grounding, and flame-signal measurement according to the manufacturer’s instructions
Answer Explanation:
Option A is correct because a furnace that ignites successfully and then shuts down with a flame-proving fault may not be detecting the established flame reliably. The flame sensor can be contaminated, improperly positioned, or affected by a poor electrical connection or inadequate grounding. The technician should follow the manufacturer’s diagnostic procedure, inspect the sensor and wiring, and measure the flame signal using the specified method. Other causes, including actual flame instability or gas-supply problems, may also require investigation if the sensor circuit checks out. Safety controls must never be bypassed to keep the furnace operating. A confirmed diagnosis helps restore reliable ignition and prevents repeated shutdowns or unsafe operation.
Why the other options are incorrect:
Option B concerns the refrigeration circuit and does not explain a furnace flame-proving fault.
Option C relates to cooling airflow and is not the first diagnostic priority for failed flame detection.
Option D changes a cooling control setting and does not address the furnace’s ignition sequence.
Quick Study Guide:
Flame-proving controls confirm that burner ignition has occurred.
Inspect the sensor, wiring, grounding, and flame signal.
Follow the furnace manufacturer’s diagnostic procedure.
Never bypass combustion safety controls to maintain operation.
Question 3. A contractor is installing a new refrigerant line set between an outdoor condensing unit and an indoor evaporator. The manufacturer’s instructions specify a maximum equivalent line length and particular requirements for pipe diameter and oil return. Which approach is most appropriate?
A. Select the largest available pipe diameter to minimize friction losses in every installation.
B. Use the existing line size regardless of the new equipment’s specifications.
C. Increase refrigerant charge until the system reaches the expected operating pressures.
D. Size and route the piping according to the equipment manufacturer’s instructions, accounting for equivalent length, elevation changes, and oil-return requirements.
Correct Answer: D. Size and route the piping according to the equipment manufacturer’s instructions, accounting for equivalent length, elevation changes, and oil-return requirements.
Answer Explanation:
Option D is correct because refrigerant piping must be selected for the specific equipment and installation conditions. Pipe diameter affects refrigerant pressure drop, mass flow, and oil return, while equivalent length accounts for the additional resistance created by fittings and other components. Elevation changes can also influence system operation, particularly where oil must return reliably to the compressor. An oversized line is not automatically better because refrigerant velocity may become insufficient for proper oil return under some operating conditions. The contractor should follow the manufacturer’s piping tables, line-length limits, and installation details, then perform the required evacuation, leak testing, and commissioning procedures. Correct piping supports equipment efficiency and compressor reliability.
Why the other options are incorrect:
Option A assumes that larger piping is always better and ignores refrigerant velocity and oil-return requirements.
Option B disregards the specifications of the newly installed equipment and the actual piping arrangement.
Option C uses refrigerant charge to compensate for a piping-design issue rather than correcting the installation.
Quick Study Guide:
Use the equipment manufacturer’s refrigerant piping specifications.
Consider equivalent length, elevation, and oil-return requirements.
Oversized refrigerant lines can create oil-return problems.
Complete required leak testing and evacuation before commissioning.
Question 4. During commissioning of a newly installed commercial ventilation system, measurements show that the supply airflow is below the design requirement. The fan rotates in the correct direction, and the motor current is within its rated operating range. The technician also finds that the duct system has several sharp transitions and undersized sections. What should be done next?
A. Increase the thermostat setpoint to compensate for insufficient airflow.
B. Evaluate the duct restrictions and system static pressure, then correct the airflow deficiencies and rebalance the system as required.
C. Replace the thermostat with a model that has a wider temperature differential.
D. Increase the refrigerant charge in the associated cooling system without further testing.
Correct Answer: B. Evaluate the duct restrictions and system static pressure, then correct the airflow deficiencies and rebalance the system as required.
Answer Explanation:
Option B is correct because undersized duct sections and abrupt transitions can increase static pressure losses and restrict the amount of air delivered by the system. Even when a fan rotates correctly and the motor current is within its rating, the installed ductwork may prevent the equipment from achieving the specified airflow. The technician should measure total external static pressure, check filters and coils, inspect dampers and duct transitions, and compare the results with the equipment’s performance data. Corrective work may include modifying restrictive duct sections, improving transitions, and balancing the distribution system. Airflow must be verified after adjustments because inadequate air movement can reduce heating or cooling performance and affect equipment reliability.
Why the other options are incorrect:
Option A changes the temperature target without correcting the physical airflow restriction.
Option C changes thermostat behavior but does not increase the duct system’s capacity.
Option D changes refrigerant charge without establishing a refrigerant-related fault.
Quick Study Guide:
Measure airflow and static pressure during system commissioning.
Undersized ducts and sharp transitions can increase resistance.
Check filters, coils, dampers, and duct dimensions before adjusting equipment.
Verify final airflow against the design requirements and equipment data.
Question 5. A technician is servicing a heat pump during mild outdoor conditions. The system operates in heating mode, but the measured supply-air temperature is lower than expected. Before adding refrigerant, the technician must determine whether the system is operating correctly and whether the refrigerant charge is appropriate. Which diagnostic approach is best?
A. Add refrigerant until the suction pressure reaches a generic target used for all heat pumps.
B. Replace the compressor because low supply-air temperature proves that it is failing.
C. Verify operating mode, airflow, outdoor conditions, refrigerant pressures and temperatures, and the manufacturer’s specified charging procedure before deciding whether the charge needs adjustment.
D. Close the outdoor coil airflow path to increase condensing pressure and raise supply-air temperature.
Correct Answer: C. Verify operating mode, airflow, outdoor conditions, refrigerant pressures and temperatures, and the manufacturer’s specified charging procedure before deciding whether the charge needs adjustment.
Answer Explanation:
Option C is correct because heat pump performance varies with outdoor temperature, indoor airflow, operating mode, defrost controls, and refrigerant-circuit conditions. A low supply-air temperature alone does not establish that the system is undercharged or that the compressor has failed. The technician should confirm the thermostat demand and reversing-valve position, inspect airflow, allow the equipment to stabilize, and collect the pressure and temperature measurements required by the manufacturer’s diagnostic procedure. Charging methods differ by equipment type and operating conditions; some systems require specified subcooling, superheat, or other manufacturer-defined methods. Accurate diagnosis prevents unnecessary refrigerant additions and helps protect system performance, efficiency, and compressor reliability.
Why the other options are incorrect:
Option A relies on a generic suction-pressure target that may be inappropriate for the equipment and operating conditions.
Option B treats one symptom as proof of compressor failure without conducting the necessary tests.
Option D deliberately restricts heat transfer and can cause unsafe operating pressures or equipment damage.
Quick Study Guide:
Heat pump performance depends on operating mode and outdoor conditions.
Verify airflow and controls before diagnosing refrigerant charge.
Use the manufacturer’s specified charging and diagnostic procedure.
Never restrict coil airflow to manipulate system pressure.